home *** CD-ROM | disk | FTP | other *** search
/ Network Support Library / RoseWare - Network Support Library.iso / pressgen / best15.txt < prev    next >
Text File  |  1992-11-27  |  3KB  |  100 lines

  1. Best Power Technology FERRUPS - Communication Port Pinouts
  2. ----------------------------------------------------------
  3.  
  4.                          FERRUPS DB-25F  
  5.  Pin                  Description
  6. -----     ---------------------------------------------------
  7.    13 <-- Common "Inverter ON" signal contact
  8. 25 <----- Contact opens on "Alarm"
  9.    12 <-- Contact closes when "Inverter On"
  10. 24 <----- Common "Alarm" signal contact
  11.    11 <-- Contact opens when "Inverter On"
  12. 23 <----- Contact closes on "Alarm"
  13.    10 <-- Humidty sensor option signal (FD and RD models only)
  14. 22 <----- Humidty sensor option signal return
  15.     9 <-- n/c
  16. 21 <----- Remote emergency power off
  17.     8 <-- n/c
  18. 20 <----- AS/400 option
  19.     7 <-- signal ground (RS232)
  20. 19 <----- n/c
  21.     6 <-- +12V level
  22. 18 <----- +12V level
  23.     5 <-- n/c
  24. 17 <----- n/c
  25.     4 <-- n/c
  26. 16 <----- n/c
  27.     3 <-- receive data (RS232)
  28. 15 <----- n/c
  29.     2 <-- transmit data (RS232
  30. 14 <----- 12V, 0.5 amp
  31.     1 <-- n/c
  32.    
  33. The "Alarm Signal Contacts" are relay contacts (rated at 25 V AC/DC 
  34. and 250mA) that change state upon any alarm condition. Contacts that close
  35. on an alarm or when the UPS is turned off are available between pins
  36. 23 and 24. Contacts that open on an alarm or when the UPS is turned off
  37. are available between pins 24 and 25.
  38.  
  39. The "Inverter On Signal Contacts" are relay contacts (rated at 25 V AC/DC 
  40. and 250mA) that change state when the inverter turns on. Contacts that
  41. close on inverter operation are available between pins 12 and 13. Contacts
  42. that open on inverter operation are available between pins 11 and 13.
  43.  
  44. The "Remote Emergency Power Off" trigger is actuated by closing a circuit 
  45. between pins 6 and 21. This will force the UPS to SystemModeOff. 
  46.  
  47. The "RS232 Communications Port" connections are found on Pin 7 (signal 
  48. ground), Pin 3 (receive data), and Pin 2 (transmit data). This port is 
  49. configured as DCE operating at 1200 baud (selectable 300, 1200, 4800, or 
  50. 9600). Data is formated in 8 bit ASCII; 1 stop bit; full duplex; no parity. 
  51. This interface supports XON/XOFF. Hardware handshaking is not supported. 
  52. Refer to TIP501 for information regarding the FERRUPS User Interface 
  53. Command Language.
  54.  
  55. FERRUPS Cable connections to a computer or terminal:
  56. ----------------------------------------------------
  57. Computer                        FERRUPS     
  58.   DB-9                           DB25
  59.   DCE                            DCE
  60. --------                        -------
  61.   RD 3 <------------------------> 2
  62.   TD 2 <------------------------> 3
  63.   SG 5 <------------------------> 7
  64.  
  65.  GND 1 <-----\
  66.  DCD 4 <-----|
  67.  DTR 6 <-----/
  68.  
  69.  RTS 7 <-----\
  70.  CTS 8 <-----/
  71.  
  72. ----------------------------------------------------
  73. Computer                        FERRUPS     
  74.   DB-25                          DB25
  75.   DTE                            DCE
  76. --------                        -------
  77.   TD 2 <------------------------> 2
  78.   RD 3 <------------------------> 3
  79.   SG 7 <------------------------> 7
  80.  
  81.  RTS 4 <-----\
  82.  CTS 5 <-----/
  83.  
  84.  DSR 6 <-----\
  85.  DCD 8 <-----|
  86.  DTR 20 <----/
  87.  
  88. ----------------------------------------------------
  89.   Modem                        FERRUPS     
  90.   DB-25                          DB25
  91.   DCE                            DCE
  92. --------                        -------
  93.   RD 3 <------------------------> 2
  94.   TD 2 <------------------------> 3
  95.   SG 7 <------------------------> 7
  96.  
  97.  RTS 4 <-----\
  98.  CTS 5 <-----/
  99.  
  100.